The Advanced Intelligent I/O Relay Output & Switch
Monitor (55000-820ADV) is an application specifi c
addressable module for use with the AxisAX Series
Intelligent Fire Alarm Control Panels. Each module is SLC
loop powered, eliminating the need for additional fi eld
wiring and external power supplies.
Designed for installation on Advanced AxisAX Series
SLC (signaling line circuit), the 55000-820ADV
provides a single initiating device circuit (IDC) input,
an independently controlled Form-C relay contact
output, and an unmonitored optically isolated voltage
input. The 55000-820ADV utilizes the Advanced unique
sub-addressing for both the independently controlled
relay and the optically isolated voltage input. By subaddressing these I/O features, AxisAX Series system point
capacities are expanded with installation, programming,
and commissioning time minimized. The 55000-820ADV
mounts to the front of a standard 4” square or 2-gang
electrical outlet box.
The IDC input of the 55000-820ADV is capable of being
wired Class A or B and can monitor a single contact
device or a group of devices. Contacts can be normally
open (N.O.) or normally closed (N.C.) ranging from heat
detectors, linear heat detectors, 4-wire conventional smoke
detectors, waterfl ow switches, tamper switches, manual
pull stations, switch input points for control, or any other
supervised input requirement. Though the IDC input can
monitor any number of contact devices, it is recommended
not to mix alarm, supervisory, or security contacts on the
same IDC module circuit.
Compatible with the AxisAX Series Dynamix I/O relationship
programming, the relay output of the 55000-820ADV
can be individually assigned to any input or output
relationship, output group, timing function, gated function,
invert operation, etc. to perform project specifi c control
operations. Ideally suitable for elevator control, HVAC
shutdown, door holder release, or similar ancillary
functions, the 55000-820ADV relay is rated 24 VDC @ 1
Amp (resistive) or 30 VAC .5 Amp (resistive).
Features:
• Supervised Initiating Device Circuit (IDC)
• Class A or B Wiring
• Independently Controlled Form-C Relay Contact
• AxisAX Series Dynamix I/O Relationship Programming
• IDC Activation Status LED
• Optically Isolated Voltage Input
• Cost-Effective & Trouble-Free Installation
Listings and Approvals:
• ETL ANSI/UL 864 Listed: 3118002NYM-001B
• UL fi le: UOXX.S7003 / ML fi le: S24460
• CSFM Approved: 7300-1713:108
• NYC MEA: 294-95-E